Title :
A distributed on-line HV transmission condition monitoring information system
Author :
Chan, W.L. ; Chan, T.M. ; Pang, S.L. ; So, A.T.P.
Author_Institution :
Hong Kong Polytech., Kowloon, Hong Kong
Abstract :
China Light and Power Company Ltd. (CLP) is responsible for supplying electricity to the whole of Hong Kong except Hong Kong Island and Lamma Island. In CLP´s Castle Peak power plant, 18 kV and 23 kV electric supplies are generated. The voltage is then stepped up to 400 kV for transmission. The intermediate control between those transformers and the major 400 kV overhead transmission system lies with a standard “one and a half breaker configuration” switch substation. The substation houses single phase encapsulated SF6 circuit breakers. In the urban centres, 400 kV substations are installed to step down 40 kV to 132 kV or further to 11 kV for distribution. This paper describes the development of an online distributed information system for monitoring the conditions of the whole HV transmission system. The system continuously monitors the status of each circuit breaker (CB) together with important operational parameters, such as duration during making and breaking, operations of hydraulic pumps and SF6 gas pressure etc. Each group of (CB) is monitored by a standalone microcontroller which is interconnected with all other microcontrollers using a local area network with a baud rate of 9600. The information can be recorded on the hard-disk of an on-site microcomputer and further transmitted back to a remote computer for alarm generation and multi-station supervision. The CLP 400 kV substation and the Tsz Wan Shan 400 kV substation are amongst the first targets for development
Keywords :
SF6 insulation; computerised monitoring; engineering information systems; gas blast circuit breakers; local area networks; microcomputer applications; power system measurement; power transmission; switching substations; 400 kV; Castle Peak power plant; China Light and Power Company; HV transmission system; Hong Kong; SF6 gas pressure; Tsz Wan Shan substation; alarm generation; circuit breaker monitoring; hydraulic pumps; information system; local area network; microcomputer; microcontroller; multi-station supervision; on-line HV transmission condition monitoring; one and a half breaker configuration; online distributed information system; overhead transmission system; single phase encapsulated SF6 circuit breakers; switching substation; urban centres; Circuit breakers; Computerized monitoring; Condition monitoring; Control systems; Distributed information systems; Microcontrollers; Power generation; Substations; Switches; Transformers;
Conference_Titel :
Transmission and Distribution Conference, 1996. Proceedings., 1996 IEEE
Conference_Location :
Los Angeles, CA
Print_ISBN :
0-7803-3522-8
DOI :
10.1109/TDC.1996.545914