DocumentCode :
228949
Title :
Application of a new method in detecting a mechanical failure associated with series capacitance change in a power transformer winding
Author :
Pham, D.A.K. ; Pham, T.M.T. ; Gockenbach, E. ; Borsi, H.
Author_Institution :
Dept. of Power Syst., Ho-Chi-Minh City Univ. of Technol., Ho Chi Minh City, Vietnam
fYear :
2014
fDate :
June 29 2014-July 3 2014
Firstpage :
1
Lastpage :
4
Abstract :
The Frequency Response Analysis (FRA) based method is expected as an efficient one in diagnosis of mechanical failures in windings of power transformers, especially in cases other testing methods cannot provide any indication for the diagnostic. However, the current FRA assessment which is based on the relevant Chinese standard and other draft international standards is not sensitive enough in detecting such failures in all cases.
Keywords :
fault diagnosis; frequency response; power transformers; transformer windings; frequency response analysis; mechanical failure; power transformer winding; series capacitance change; Electrical resistance measurement; Frequency measurement; Resistance; Thickness measurement; Windings; Frequency Response Analysis; mechanical failure; transformer winding; winding series capacitance;
fLanguage :
English
Publisher :
ieee
Conference_Titel :
Dielectric Liquids (ICDL), 2014 IEEE 18th International Conference on
Conference_Location :
Bled
Type :
conf
DOI :
10.1109/ICDL.2014.6893098
Filename :
6893098
Link To Document :
بازگشت