• DocumentCode
    228968
  • Title

    Study on influence of oxidation on static electrification in transformer oil

  • Author

    Shima, Keisuke ; Tsuchie, M. ; Kozako, Masahiro ; Hikita, Masayuki ; Gosho, Yoshihiro

  • Author_Institution
    Fac. of Eng., Kyushu Inst. of Technol., Fukuoka, Japan
  • fYear
    2014
  • fDate
    June 29 2014-July 3 2014
  • Firstpage
    1
  • Lastpage
    4
  • Abstract
    In oil-immersed transformers, static electrification phenomenon is caused by insulating oil flowing on solid insulator such as pressboard (PB). In Japan, as a countermeasure, 1, 2, 3-benzotriazol (BTA) is used to suppress static electrification. But, recent years, it has been reported that static electrification phenomenon increases with aging owing to oxidation of insulating oil, operation history of transformers with overhaul, and so on [1]. This paper deals with the verification of BTA effect on the increase of electrostatic charging tendency (ECT) due to aging, and evaluation for the influence of air exposure on static electrification during overhaul using the aging oil from 500 kV transformer by performing overhaul process according to actual operation and accelerated aging test.
  • Keywords
    ageing; oxidation; power transformers; static electrification; transformer oil; BTA; ECT; Japan; benzotriazol; electrostatic charging tendency; insulating oil; oil-immersed transformers; oxidation influence; pressboard; solid insulator; static electrification; transformer oil; voltage 500 kV; Accelerated aging; Heating; Power transformer insulation; Time measurement; BTA; electrostatic charging tendency; insulating oil; static electrification; transformer; volume resistivity;
  • fLanguage
    English
  • Publisher
    ieee
  • Conference_Titel
    Dielectric Liquids (ICDL), 2014 IEEE 18th International Conference on
  • Conference_Location
    Bled
  • Type

    conf

  • DOI
    10.1109/ICDL.2014.6893109
  • Filename
    6893109