Abstract :
It has long been the accepted opinion that it is the DBDS additive that causes the majority of failures in modern transformers manufactured up to 2007 when the use of this antioxidant was discontinued by most of the oil manufacturers that had chosen to use DBDS. Since long, whenever a failure occurs and the Covered Conductor Deposition test (CCD) comes out positive, DBDS is blamed. However, this enormous simplification of reality has not been accepted by all. Independent research has been carried out for the purpose of giving a less prejudice picture of the situation. With this research results, in conjunction with the in-depth failure analysis of one transformer that presented all the signs which characterize a corrosive sulfur it has become clear that corrosive sulfur failure depending on DBDS and other sulfur based additives may well be a myth. The same research also strongly indicate that Irgamet® 39 cannot possibly be a copper passivator and this is exemplified by purely logical reasoning. This paper also briefly discuss stereochemical and as far as literature searches performed by the authors never before mentioned aspect regarding why lrgamet® 39 will never function. Irgamet® 39 was used to attempt to mitigate the corrosive sulphur effect by DBDS in this transformer which failed. Stereo-chemistry, molecule reactivity and literature searches has instead shown DBDS to be a passivator in the true sense or the word.
Keywords :
additives; conductors (electric); corrosion; failure analysis; organic compounds; power transformer insulation; power transformer testing; sulphur; transformer oil; CCD testing; DBDS additive; Irgamet 39; antioxidant; copper passivator; corrosive sulfur failure analysis; covered conductor deposition testing; dibenzyl disulphide; oil manufacturer; stereochemical; stereochemistry; transformer; Additives; Chemicals; Copper; Media; Nitrogen; Silicon; Antioxidant; BHT; Benzo-tri-azole (BTA); DBDS; Irgamet® 39; active sulfur; copper corrosion inhibitor; copper in cellulose; copper sulphidation; corrosive sulfur; joint; oxidation inhibitor; soldering; sulfur in cellulose; transformer failure; weld; winding turn to winding turn flashover;
fLanguage :
English
Publisher :
ieee
Conference_Titel :
Dielectric Liquids (ICDL), 2014 IEEE 18th International Conference on
Conference_Location :
Bled
Type :
conf
DOI :
10.1109/ICDL.2014.6893140
Filename :
6893140
Link To Document :
بازگشت