• DocumentCode
    2291293
  • Title

    X-ray induced partial discharge testing of full-size EHV insulators

  • Author

    Braun, J.M. ; Rizzetto, S. ; Fujimoto, N. ; Ford, G.L. ; Molony, T. ; Meehan, J.P.

  • Author_Institution
    Ontario Hydro Technol., Toronto, Ont., Canada
  • fYear
    1996
  • fDate
    15-20 Sep 1996
  • Firstpage
    197
  • Lastpage
    203
  • Abstract
    A new partial discharge (PD) measurement system has been assembled which takes advantage of modern ultrawideband instrumentation techniques and which eliminates the influence of statistical time lags on partial discharge initiation processes. The PD test system is designed to accommodate full size 550 kV insulators used in gas-insulated substations (GIS) at up to 800 kV at high sensitivity. The system is intended to improve the effectiveness of factory PD testing, thereby increasing GIS reliability. The system uses X-ray irradiation of the test object to eliminate the statistical time lag during PD measurement. Under X-ray irradiation the PD pulse repetition rate is increased and the discharge inception voltage (DIV) is sharply reduced. The DIV of some insulators under X-ray irradiation was recorded at values more than an order of magnitude lower than without X-rays. The XIPD technology is generic and can be readily extended to a broad range of insulation systems and equipment. The practical implications of this technology on acceptance testing of insulators is also discussed
  • Keywords
    charge measurement; gas insulated substations; insulator testing; insulators; partial discharges; 550 kV; 800 kV; EHV insulators; GIS; X-ray induced partial discharge testing; X-ray irradiation; discharge inception voltage; gas-insulated substations; high sensitivity; partial discharge initiation processes; partial discharge measurement; statistical time lags; ultrawideband instrumentation; void discharge; Assembly systems; Geographic Information Systems; Instruments; Insulation; Insulator testing; Partial discharge measurement; Partial discharges; System testing; Time measurement; Ultra wideband technology;
  • fLanguage
    English
  • Publisher
    ieee
  • Conference_Titel
    Transmission and Distribution Conference, 1996. Proceedings., 1996 IEEE
  • Conference_Location
    Los Angeles, CA
  • Print_ISBN
    0-7803-3522-8
  • Type

    conf

  • DOI
    10.1109/TDC.1996.545935
  • Filename
    545935