DocumentCode
2293542
Title
Application of surge arresters to a 115-kV circuit
Author
Short, T.A. ; Warren, C.A. ; Burke, J.J. ; Burns, C.W. ; Godlewski, J.R. ; Graydon, F., Jr. ; Morosini, H.
Author_Institution
Power Technol. Inc., Schenectady, NY, USA
fYear
1996
fDate
15-20 Sep 1996
Firstpage
276
Lastpage
282
Abstract
Momentary interruptions caused by lightning were a severe problem for a Champion International paper mill in upstate New York. Following a detailed investigation, the Niagara Mohawk Power Corporation (NMPC) installed line surge arresters to the supply circuit to eliminate lightning-caused interruptions. The paper mill is supplied by a 115-kV circuit which was characterized by low insulation level and poor grounding. Lightning arresters were found to be the best solution. Extensive line performance monitoring of the circuit performed before and after the arresters were installed has provided some valuable information. The arresters have successfully eliminated the lightning-caused interruptions
Keywords
arresters; industrial power systems; lightning protection; paper industry; power system protection; 115 kV; Champion International paper mill; New York; Niagara Mohawk Power Corporation; lightning protection; lightning-caused interruptions elimination; line performance monitoring; low insulation level; poor grounding; supply circuit; surge arresters application; Arresters; Circuits; Insulation; Lightning; Milling machines; Monitoring; Paper mills; Poles and towers; Power quality; Surge protection;
fLanguage
English
Publisher
ieee
Conference_Titel
Transmission and Distribution Conference, 1996. Proceedings., 1996 IEEE
Conference_Location
Los Angeles, CA
Print_ISBN
0-7803-3522-8
Type
conf
DOI
10.1109/TDC.1996.545947
Filename
545947