• DocumentCode
    2295
  • Title

    A Straightforward Method for Wide-Area Fault Location on Transmission Networks

  • Author

    Azizi, Sadegh ; Sanaye-Pasand, Majid

  • Author_Institution
    Sch. of Electr. & Comput. Eng., Univ. of Tehran, Tehran, Iran
  • Volume
    30
  • Issue
    1
  • fYear
    2015
  • fDate
    Feb. 2015
  • Firstpage
    264
  • Lastpage
    272
  • Abstract
    Local practices in fault location require measurements from one or more terminals of the faulted line to be available. On the other hand, the nonlinearity of circuit equations associated with wide-area fault location makes their solving process iterative and computationally demanding. This paper proposes a non-iterative method for wide-area fault location by taking advantage of the substitution theorem. Accordingly, a system of equations is constructed which can be easily solved using the linear least-squares method. The distributed-parameter line model is considered to provide a highly accurate estimation. Besides, due to inherent errors of current transformers, the current data is not taken into account to preserve the accuracy. In order to avoid uncertainties in relation with construction of zero-sequence network, just positive- and negative-sequence networks are exploited. Nonetheless, the method still is capable of pinpointing all types of short-circuit faults by using a restricted number of synchronized pre- and post-fault voltage phasors. Numerous simulation studies conducted on the WSCC 9-bus and New England 39-bus test systems verify the effectiveness and applicability of the proposed fault location method, even with limited coverage of synchronized measurements.
  • Keywords
    current transformers; fault location; iterative methods; least squares approximations; phasor measurement; power transmission faults; short-circuit currents; New England 39-bus test system; WSCC 9-bus test system; circuit equation nonlinearity; current transformer; distributed-parameter line model; iterative process; linear least square method; negative-sequence network; noniterative method; positive-sequence network; short-circuit fault; substitution theorem; synchronized post-fault voltage phasor measurement; transmission network; uncertainty avoidance; wide-area fault location; zero-sequence network; Circuit faults; Equations; Fault location; Impedance; Mathematical model; Power transmission lines; Transmission line measurements; Phasor measurement unit (PMU); sequence network; substitution theorem; wide-area fault location;
  • fLanguage
    English
  • Journal_Title
    Power Delivery, IEEE Transactions on
  • Publisher
    ieee
  • ISSN
    0885-8977
  • Type

    jour

  • DOI
    10.1109/TPWRD.2014.2334471
  • Filename
    6867388