DocumentCode :
229739
Title :
Empirical study of system-level PV power plant power factor adjustment relying on PV inverter
Author :
Lv Zhenhua ; Shi Mingming ; Yuan Xiaodong
fYear :
2014
fDate :
22-25 Oct. 2014
Firstpage :
840
Lastpage :
842
Abstract :
A experiment of photovoltaic inverter helping power facotr adjustment of PV power station is carried on. A SVG is connected to the 10kV bus bar of 30MWp PV power station in parallel. The effect of photovoltaic inverter on PV power station power factor regulation is studied on the adjustment of photovoltaic inverter with SVG offerring reactive power violation. Through the trial, we found the PV power station power factor regulation can be achieved by photovoltaic inverter, but the adjustment is slower, and oscillation phenomenon occurs when multiple inverters adjust. The test results can provide reference to the technology development of the photovoltaic inverter.
Keywords :
busbars; invertors; photovoltaic power systems; power factor; reactive power; PV inverter; PV power station power factor regulation; SVG; busbar; oscillation phenomenon; photovoltaic inverter; power 30 MW; reactive power violation; system-level PV power plant power factor adjustment; voltage 10 kV; Inverters; Photovoltaic systems; Reactive power; Voltage control;
fLanguage :
English
Publisher :
ieee
Conference_Titel :
Electrical Machines and Systems (ICEMS), 2014 17th International Conference on
Conference_Location :
Hangzhou
Type :
conf
DOI :
10.1109/ICEMS.2014.7013585
Filename :
7013585
Link To Document :
بازگشت