Title :
3D steady-state thermal load analysis of the bus-bar in large-scale generator with evaporative cooling system
Author :
Jinxiu Chen ; Haihong Dong ; Lin Ruan
Author_Institution :
Inst. of Electr. Eng., Beijing, China
fYear :
2014
fDate :
22-25 Oct. 2014
Firstpage :
2365
Lastpage :
2368
Abstract :
In hydro-generator, stator bus bar is a vital electrical part and the overheating problem of it is one of the common accidents in hydro-generator. Based on the characteristics of evaporative cooling technology, reliability of large-scale hydro-generator would be enhanced if applying evaporative cooling technology to the stator bus bar. Because of the complex construction of bus bars, copper loss, as the driving force of self-circulation evaporative cooling system of bus bar, has an uneven and complicated distribution. Firstly, this paper briefly introduces evaporative cooling technology and points out several advantages and research difficulties of evaporative cooling stator bus bar. Secondly, based on theory model of eddy current and the finite element calculation software, 3D steady-state copper losses of a group of bus bars with typical structure are calculated. According to the calculation results, characteristics of thermal load distributions of bus bars with typical structure will be summed up.
Keywords :
busbars; cooling; finite element analysis; load distribution; stators; 3D steady-state thermal load analysis; copper loss; eddy current; finite element calculation software; hydro-generator; large-scale generator; self-circulation evaporative cooling system; stator bus bar; Bars; Coolants; Eddy currents; Magnetic fields; Stators; Three-dimensional displays;
fLanguage :
English
Publisher :
ieee
Conference_Titel :
Electrical Machines and Systems (ICEMS), 2014 17th International Conference on