• DocumentCode
    230099
  • Title

    Suppression of sub-synchronous oscillation caused by HVDC using supplementary excitation damping controller

  • Author

    Xinghua Dong ; Xiuhe Wang ; Yubo Yang

  • Author_Institution
    Coll. of Electr. Eng., Shandong Univ., Jinan, China
  • fYear
    2014
  • fDate
    22-25 Oct. 2014
  • Firstpage
    2431
  • Lastpage
    2434
  • Abstract
    Two kinds of mechanism that cause Sub-synchronous Oscillation (SSO) by High Voltage Direct Current (HVDC) are introduced in this paper. The Unit Interaction Factor (UIF) and the test signal method are used to analyze SSO that caused by HVDC. The results show that when UIF>0.1, the simulation model takes the risk of SSO. Then, supplementary excitation damping controller (SEDC) is used to suppress the HVDC-SSO. The simulation results show that the SEDC designed has good damping effect on HVDC-SSO.
  • Keywords
    HVDC power convertors; HVDC power transmission; damping; oscillations; power transmission control; HVDC; high voltage direct current; subsynchronous oscillation; supplementary excitation damping controller; test signal method; unit interaction factor; Benchmark testing; Damping; Generators; HVDC transmission; Rectifiers; Shafts; Torque;
  • fLanguage
    English
  • Publisher
    ieee
  • Conference_Titel
    Electrical Machines and Systems (ICEMS), 2014 17th International Conference on
  • Conference_Location
    Hangzhou
  • Type

    conf

  • DOI
    10.1109/ICEMS.2014.7013913
  • Filename
    7013913