DocumentCode
2314160
Title
Effects of SMES Equipped UPFC on Distance Relay Tripping Characteristic
Author
Jamali, S. ; Kazemi, A. ; Shateri, H.
Author_Institution
Dept. of Electr. Eng., Iran Univ. of Sci. & Technol. (IUST), Tehran
fYear
2008
fDate
12-15 Oct. 2008
Firstpage
1
Lastpage
7
Abstract
This paper presents the measured impedance at the relaying point in the presence of unified power flow controller (UPFC), one of flexible alternating current transmission system (FACTS) devices, which is equipped with a superconductor magnetic energy storage (SMES) system. The presence of SMES equipped UPFC on a transmission line greatly influences the measured impedance at the relaying point. The measured impedance itself depends on the power system structural conditions, pre-fault loading, and especially the ground fault resistance. In the presence of SMES equipped UPFC, its structural and controlling parameters as well as its installation location affects the measured impedance. Here, the measured impedance at the relaying point is presented due to the mentioned affecting parameters.
Keywords
flexible AC transmission systems; load flow control; distance relay tripping; flexible alternating current transmission system; superconductor magnetic energy storage; unified power flow controller; Current measurement; Electrical resistance measurement; Impedance measurement; Power measurement; Power system relaying; Protective relaying; Samarium; Superconducting magnetic energy storage; Superconducting transmission lines; Transmission line measurements; Distance protection; FACTS devices; Fault resistance; Measured impedance; SMES; UPFC;
fLanguage
English
Publisher
ieee
Conference_Titel
Power System Technology and IEEE Power India Conference, 2008. POWERCON 2008. Joint International Conference on
Conference_Location
New Delhi
Print_ISBN
978-1-4244-1763-6
Electronic_ISBN
978-1-4244-1762-9
Type
conf
DOI
10.1109/ICPST.2008.4745270
Filename
4745270
Link To Document