• DocumentCode
    2314909
  • Title

    Diagnostic testing of oil-impregnated paper insulation in prorated power transformers under accelerated stress

  • Author

    Pradhan, Manoj K. ; Ramu, T.S.

  • Author_Institution
    Dept. of High Voltage Eng., Indian Inst. of Sci., Bangalore, India
  • fYear
    2004
  • fDate
    19-22 Sept. 2004
  • Firstpage
    66
  • Lastpage
    69
  • Abstract
    In the recent past, a considerable amount of work has been published on the dynamics of aging of oil impregnated paper (OIP) insulation in transformers. The insulation is always subjected to stresses of different types at the same point in time. Among the more important stress are, electrical, thermal and their combination. Insulating properties of both solid (cellulose paper) and liquid (mineral insulating oil) phases deteriorate with time due to an electrothermal process called aging. The status of insulation at a given point in time can therefore be assessed by monitoring such of those properties of insulation which are sensitive to the amount of aging, so as to be able to take and appropriate corrective measures to avoid/postpone impending insulation failure. This procedure, called diagnostic testing and condition monitoring (DTCM) aims to avoid catastrophic failure. The aim of the present investigation is to try and determine the most sensitive parameters which can serve as indices of aging and hence as a reasonably accurate indicator of possible imminent failure of apparatus insulation in service. To this end, carefully controlled laboratory aging experiments have been performed on about eight nominally identical and scaled-down models of prorated units incorporating all the essential features of actual power transformers under normal operating electric stress and accelerated thermal stress. The paper details the DTCM program designed to acquire aging data.
  • Keywords
    ageing; condition monitoring; impregnated insulation; insulation testing; life testing; paper; power transformer insulation; power transformer testing; thermal stresses; transformer oil; accelerated stress; aging; catastrophic failure; cellulose paper; diagnostic testing and condition monitoring; electrical stress; electrothermal process; mineral insulating oil; oil-impregnated paper insulation; prorated power transformer; thermal stress; transformer insulation; Aging; Condition monitoring; Insulation testing; Life estimation; Oil insulation; Petroleum; Power transformer insulation; Power transformers; Solids; Thermal stresses;
  • fLanguage
    English
  • Publisher
    ieee
  • Conference_Titel
    Electrical Insulation, 2004. Conference Record of the 2004 IEEE International Symposium on
  • ISSN
    1089-084X
  • Print_ISBN
    0-7803-8447-4
  • Type

    conf

  • DOI
    10.1109/ELINSL.2004.1380452
  • Filename
    1380452