• DocumentCode
    2318001
  • Title

    VHF PD detection of 110 kV XLPE cable accessories

  • Author

    Wang, Wei ; Wei, Bin ; Li, Chengrong ; Ding, Lijian ; Li, Changyu ; Liu, Dong

  • Author_Institution
    Sch. of Electr. Eng., North China Electr. Power Univ., Baoding, China
  • fYear
    2004
  • fDate
    19-22 Sept. 2004
  • Firstpage
    366
  • Lastpage
    371
  • Abstract
    Partial discharge (PD) can indicate defects in HV XLPE cable accessories. A new land of split-core PD sensor is designed that can be easy installed on-site and used safely, and has a bandwidth from 3 MHz to 60 MHz. A model of a cable accessory was made and some typical PD phenomena in this accessory were simulated, such as sliding discharge, floating discharge and cavity discharge. PD tests were made to find the features of the defects. The data from the tests were analyzed and the spectra of different types of PD were plotted using statistical parameters to reveal the feature of the different patterns of PD. The split-core PD sensor has been used on-site after sample testing in the laboratory. More than twenty cases of on-line PD detection for 110 kV XLPE cables have been obtained.
  • Keywords
    XLPE insulation; insulation testing; partial discharge measurement; power cable insulation; power cable testing; sensors; 110 kV; 3 to 60 MHz; PD detection; PD spectra; PD test; VHF; XLPE cable accessories; cavity discharge; floating discharge; partial discharge; sliding discharge; split-core PD sensor; statistical parameters; very high frequency; Cable insulation; Cable shielding; Cables; Coils; Electromagnetic coupling; Magnetic cores; Magnetic sensors; Magnetic shielding; Partial discharges; Testing;
  • fLanguage
    English
  • Publisher
    ieee
  • Conference_Titel
    Electrical Insulation, 2004. Conference Record of the 2004 IEEE International Symposium on
  • ISSN
    1089-084X
  • Print_ISBN
    0-7803-8447-4
  • Type

    conf

  • DOI
    10.1109/ELINSL.2004.1380598
  • Filename
    1380598