Title :
Experimental model of aging mechanisms of on-load tap changer contacts
Author :
Erbrink, Jur J. ; Gulski, Edward ; Smit, Johan J. ; Seitz, Paul P. ; Leich, Rory
Author_Institution :
Delft Univ. of Technol., Delft
Abstract :
It is known that most failure of power transformers are related to aging effects of the on-load tap changer contacts. To understand the aging mechanisms and to develop knowledge rules to interpret different failure mechanisms a test model has been developed. In particular, the effect of the several aging stages of tap changer change-over selector contacts on dynamic resistance measurements (DRM) has been considered, by several measurements with aged tap changer contacts. These aging phases include clean contacts, contacts with an oil film layer, contacts with coking and contacts with pitting. Based on these experiments it is shown that the DRM method is very sensitive to aged change-over selector contacts of an on-load tap changer. In addition to laboratory experiments, the same measurements are performed on naturally aged change-over selector contacts at a Dutch utility.
Keywords :
electric resistance measurement; electrical contacts; failure analysis; on load tap changers; aging mechanisms; dynamic resistance measurements; failure mechanisms; on-load tap changer contacts; power transformers; Aging; Electrical resistance measurement; Failure analysis; Laboratories; On load tap changers; Particle measurements; Performance evaluation; Petroleum; Power transformers; Testing; aging; contact resistance; contacts; diagnostic expert systems; dynamic response; power transformers; resistance measurement;
Conference_Titel :
Condition Monitoring and Diagnosis, 2008. CMD 2008. International Conference on
Conference_Location :
Beijing
Print_ISBN :
978-1-4244-1621-9
Electronic_ISBN :
978-1-4244-1622-6
DOI :
10.1109/CMD.2008.4580273