DocumentCode
2318259
Title
Thermal failure of transformers
Author
Kulshreshtha, Arvind
Author_Institution
Bharat Heavy Electricals Ltd. Jhansi, Jhansi
fYear
2008
fDate
21-24 April 2008
Firstpage
280
Lastpage
283
Abstract
The thermal failure in high voltage equipment is little heard and is generally known to have the slow & deteriorating effect on the insulation system, which ultimately reduce the life of the equipment. In a unique classical case, 9 units of 100 MVA 230/110/11 kV oil filled auto transformers supplied to one of the electrical utility in India failed in quick succession due to oil starvation in a particular part of the winding leading to thermal failure of complete lot of 9 nos. transformers at sites. In spite of oil starvation, the transformer withstood the voltage and passed all the dielectric tests successfully, which concludes that the dielectric failure had not occurred. The failure due to thermal failure was further confirmed by the different degrees of blackening of cellulose insulation depending upon the time, it has put into service. In this paper, findings of the studies made and corrective measures taken to avert such failures have been discussed & detailed.
Keywords
transformer insulation; transformer testing; India; cellulose insulation blackening; dielectric tests; high voltage equipment; insulation system; oil filled auto transformers; oil starvation; transformer thermal failure; voltage 11 kV; voltage 110 kV; voltage 230 kV; Chemicals; Circuits; Coils; Dielectric losses; Dielectrics and electrical insulation; Impedance; Oil insulation; Petroleum; Power transformer insulation; Temperature; FTIR spectra; SiO2 ; leakage current; n-octadecyltrichlorosilane;
fLanguage
English
Publisher
ieee
Conference_Titel
Condition Monitoring and Diagnosis, 2008. CMD 2008. International Conference on
Conference_Location
Beijing
Print_ISBN
978-1-4244-1621-9
Electronic_ISBN
978-1-4244-1622-6
Type
conf
DOI
10.1109/CMD.2008.4580281
Filename
4580281