Abstract :
The breakdown and the corona inception voltages experiments of SF6/CF4 mixtures in non-uniform field were performed. The experiments were carried out under AC, positive and negative standard lightning impulse (SLI) voltages. The point-plane electrode was used to make non-uniform field and gap distance was 3 mm. SF6/CF4 mixtures pressure ranged from 0.1 to 0.5 MPa and the percentage of SF6 and CF4 was 0, 20, 40, 60, 80 and 100%. Under positive SLI the breakdown voltage was increased slowly as pressure increasing but under negative SLI the breakdown voltage was increased slightly as pressure increasing. At low pressure the breakdown voltage of positive and negative SLI was similar. Under AC voltage the breakdown voltage was increased linearly but the corona inception voltage was saturated over 0.2 MPa. This paper suggests elementary data in gas insulated systems.
Keywords :
SF6 insulation; corona; electric breakdown; gas insulated switchgear; corona inception voltages; gas insulated systems; nonuniform field breakdown characteristics; point-plane electrodes; pressure 0.1 MPa to 0.5 MPa; standard lightning impulse voltages; AC generators; Breakdown voltage; Corona; Dielectric breakdown; Electric breakdown; Electrodes; Partial discharges; Sulfur hexafluoride; Testing; Voltage measurement; Corona; Dielectric Breakdown; SF6;
fLanguage :
English
Publisher :
ieee
Conference_Titel :
Condition Monitoring and Diagnosis, 2008. CMD 2008. International Conference on
Conference_Location :
Beijing
Print_ISBN :
978-1-4244-1621-9
Electronic_ISBN :
978-1-4244-1622-6
Type :
conf
DOI :
10.1109/CMD.2008.4580297
Filename :
4580297
Link To Document :
بازگشت