Title :
Multi-PD sources location by UWB RF detection on power transformers and a case study on-site
Author :
Zhiguo, Tang ; Wenzhi, Chang ; Chengrong, Li ; Caixiong, Wang ; Zhong, Zheng ; Kang, Sheng
Author_Institution :
Beijing Key Lab. of High Voltage&EMC, North China Electr. Power Univ., Beijing
Abstract :
Ultra-wideband (UWB) RF sensor-array PD location is a novel technology based on antenna array detection and time-difference algorithm for power transformers. It has demonstrated high sensitivity and accuracy for single PD source by experiments in laboratory. In this paper, a further study has been carried out for multi-PD sources location using the UWB RF sensor array PD location method. Moreover, a practical location case is given on a real transformer. The results indicate that the method presented in the paper is effective for multi-PD source location and has promising future in real transformers.
Keywords :
antenna arrays; electric sensing devices; partial discharges; power transformers; ultra wideband technology; UWB RF detection; multiPD sources location; power transformers; ultrawideband RF sensor-array PD location; Condition monitoring; Frequency estimation; Iron; Laboratories; Oil insulation; Partial discharges; Position measurement; Power transformers; Radio frequency; Sensor arrays; Multi-PD source Location; On-site; Partial discharge; Power Transformer;
Conference_Titel :
Condition Monitoring and Diagnosis, 2008. CMD 2008. International Conference on
Conference_Location :
Beijing
Print_ISBN :
978-1-4244-1621-9
Electronic_ISBN :
978-1-4244-1622-6
DOI :
10.1109/CMD.2008.4580342