Experience with PD measurements in GIS maintenance concept
Author :
Meijer, S. ; Smit, J.J. ; Kanters, A.J.L.M.
Author_Institution :
Delft Univ. of Technol., Delft
Abstract :
Since the early nineties, ultra-high-frequency (UHF) partial discharge (PD) measurements are being applied to SF6 gas-insulated equipment. Over the years, PD measurements revealed the presence of some insulation defects in the 380 kV GIS. The measuring results have been compared to laboratory experiments. Moreover, locating was possible as well. Cigre TF D1.03.09 has been working on a risk-assessment procedure to assess the risk for a failure for insulation defects, based on PD measurements. So this procedure is only applicable to insulation defects that give detectable PD activity. The paper will show examples of the application of this risk assessment method on the different detected PD sources. Finally the actions initiated by the DSO/TSO for these analyzed insulation defects will be described.
Keywords :
SF6 insulation; gas insulated substations; maintenance engineering; partial discharge measurement; risk management; Cigre TF Dl.03.09; GIS maintenance; PD measurements; SF6 gas-insulated equipment; insulation defects; risk-assessment; ultra-high-frequency partial discharge measurements; Breakdown voltage; Circuits; Electric breakdown; Frequency; Geographic Information Systems; Insulation; Partial discharge measurement; Partial discharges; Risk management; UHF measurements; Gas-Insulated Substation; Non-Conventional Detection; Partial Discharges; Risk Assessment; Ultra-High Frequency;
Conference_Titel :
Condition Monitoring and Diagnosis, 2008. CMD 2008. International Conference on
Conference_Location :
Beijing
Print_ISBN :
978-1-4244-1621-9
Electronic_ISBN :
978-1-4244-1622-6
DOI :
10.1109/CMD.2008.4580347