DocumentCode
2319479
Title
Insulation condition assessment of transformer bushings by means of polarisation/depolarisation current analysis
Author
Bhumiwat, Supatra A.
Author_Institution
KEA Consultant, Auckland, New Zealand
fYear
2004
fDate
19-22 Sept. 2004
Firstpage
500
Lastpage
503
Abstract
This paper presents some practical experience of polarisation/depolarisation current (PDC) analysis on a number of condenser bushings having three different insulation designs-oil impregnated paper (OIP), synthetic resin bonded paper (SRBP) and resin impregnated paper (RIP). It suggests methods for performing successful on-site measurement. The document contains PDC measurement results and evaluation results of main insulation C1 for each type of bushing. It proves that the sensitivity in detecting insulation aging of the PDC technique is better than the conventional 50 Hz test.
Keywords
ageing; bushings; condition monitoring; impregnated insulation; partial discharge measurement; polarisation; resins; transformer oil; 50 Hz; PDC measurement; condenser bushings; insulation aging; insulation condition assessment; insulation designs; oil impregnated paper; on-site measurement; polarisation-depolarisation current analysis; resin impregnated paper; synthetic resin bonded paper; transformer bushings; Bonding; Insulators; Moisture; Oil insulation; Petroleum; Polarization; Power transformer insulation; Power transformers; Resins; Testing;
fLanguage
English
Publisher
ieee
Conference_Titel
Electrical Insulation, 2004. Conference Record of the 2004 IEEE International Symposium on
ISSN
1089-084X
Print_ISBN
0-7803-8447-4
Type
conf
DOI
10.1109/ELINSL.2004.1380664
Filename
1380664