• DocumentCode
    2319479
  • Title

    Insulation condition assessment of transformer bushings by means of polarisation/depolarisation current analysis

  • Author

    Bhumiwat, Supatra A.

  • Author_Institution
    KEA Consultant, Auckland, New Zealand
  • fYear
    2004
  • fDate
    19-22 Sept. 2004
  • Firstpage
    500
  • Lastpage
    503
  • Abstract
    This paper presents some practical experience of polarisation/depolarisation current (PDC) analysis on a number of condenser bushings having three different insulation designs-oil impregnated paper (OIP), synthetic resin bonded paper (SRBP) and resin impregnated paper (RIP). It suggests methods for performing successful on-site measurement. The document contains PDC measurement results and evaluation results of main insulation C1 for each type of bushing. It proves that the sensitivity in detecting insulation aging of the PDC technique is better than the conventional 50 Hz test.
  • Keywords
    ageing; bushings; condition monitoring; impregnated insulation; partial discharge measurement; polarisation; resins; transformer oil; 50 Hz; PDC measurement; condenser bushings; insulation aging; insulation condition assessment; insulation designs; oil impregnated paper; on-site measurement; polarisation-depolarisation current analysis; resin impregnated paper; synthetic resin bonded paper; transformer bushings; Bonding; Insulators; Moisture; Oil insulation; Petroleum; Polarization; Power transformer insulation; Power transformers; Resins; Testing;
  • fLanguage
    English
  • Publisher
    ieee
  • Conference_Titel
    Electrical Insulation, 2004. Conference Record of the 2004 IEEE International Symposium on
  • ISSN
    1089-084X
  • Print_ISBN
    0-7803-8447-4
  • Type

    conf

  • DOI
    10.1109/ELINSL.2004.1380664
  • Filename
    1380664