DocumentCode
2319585
Title
Application of GPS based fault location scheme for distribution system
Author
Bo, Z.Q. ; Weller, G. ; Jiang, F. ; Yang, Q.X.
Author_Institution
GEC TD Alsthom P&C Ltd., UK
Volume
1
fYear
1998
fDate
18-21 Aug 1998
Firstpage
53
Abstract
This paper presents the application of transient based fault location techniques to the distribution system by utilising the Global Positioning System (GPS). In the scheme, the proposed locator, which contains a specially designed fault transient detection device, a GPS receiver, is connected to the power line through a coupling capacitor. The locator installed at each busbar in a distribution network is used to capture the fault generated high frequency voltage transient signals and records the instance (GPS time) when the initial travelling wave generated by the fault arrives. The exact fault position is determined by comparing between the instances in time when the fault arrives at each locator location. Extensive simulation studies presented in the paper prove the feasibility of the scheme
Keywords
Global Positioning System; busbars; fault location; power distribution faults; power system transients; GPS based fault location; GPS receiver; Global Positioning System; coupling capacitor; distribution network busbar; distribution system; exact fault position; fault generated high frequency voltage transient signals; fault transient detection device; initial travelling wave; transient based fault location techniques; Detectors; Electrical fault detection; Fault detection; Fault location; Frequency; Global Positioning System; Power system protection; Power system transients; Signal generators; Voltage;
fLanguage
English
Publisher
ieee
Conference_Titel
Power System Technology, 1998. Proceedings. POWERCON '98. 1998 International Conference on
Conference_Location
Beijing
Print_ISBN
0-7803-4754-4
Type
conf
DOI
10.1109/ICPST.1998.728713
Filename
728713