• DocumentCode
    2320423
  • Title

    The effect of temperature and humidity on corona inception voltage gradient of UHV DC transmission line

  • Author

    Wang, Wei ; Li, Chengrong ; Luo, Bing ; Li, Xiaolin ; Jiang, Yitao ; An, Bing ; Wang, Yixu

  • Author_Institution
    Beijing Key Lab. of High Voltage&EMC, North China Electr. Power Univ., Beijing
  • fYear
    2008
  • fDate
    21-24 April 2008
  • Firstpage
    816
  • Lastpage
    818
  • Abstract
    To research the effect of temperature and humidity on corona inception voltage gradient of UHV DC transmission line, a mini corona cage has been constructed and put in a manual environment room, which temperature and humidity can be controlled. At the same time, a corona inception voltage gradient measuring system by using vary methods such as current impulse method, acoustic method have been set up too. The corona inception voltage gradient of a copper line have been measured in a mini corona cage not only at different absolute humidity from 3 g/m3 to 12 g/m3 but also at different temperature from 0degC to 35degC. The relationship between corona inception voltage gradient and temperature and humidity have been achieved.
  • Keywords
    HVDC power transmission; corona; humidity; power transmission lines; temperature; UHV DC transmission line; corona inception voltage gradient; temperature-humidity effect; Acoustic measurements; Corona; Current measurement; Humidity control; Temperature control; Time measurement; Transmission line measurements; Transmission lines; Voltage control; Voltage measurement; Corona; DC; Effect; Hunidity; Temperature;
  • fLanguage
    English
  • Publisher
    ieee
  • Conference_Titel
    Condition Monitoring and Diagnosis, 2008. CMD 2008. International Conference on
  • Conference_Location
    Beijing
  • Print_ISBN
    978-1-4244-1621-9
  • Electronic_ISBN
    978-1-4244-1622-6
  • Type

    conf

  • DOI
    10.1109/CMD.2008.4580409
  • Filename
    4580409