• DocumentCode
    2320789
  • Title

    Experiences of dielectric response measurement in frequency domain for diagnostics of transformer insulation system

  • Author

    Ramakichenan, V. ; Jain, Rahul Kumar ; Sethumadhavan, Thekkeveetil ; Chaudhari, Sushil E. ; Venkatasami, A. ; Chandle, Jayalakshmi

  • Author_Institution
    CG Global R&D Centre, Crompton Greaves Ltd., Mumbai
  • fYear
    2008
  • fDate
    21-24 April 2008
  • Firstpage
    914
  • Lastpage
    918
  • Abstract
    Moisture and aging strongly influence the dielectric properties of composite oil/cellulose insulation system used in power transformer. So the knowledge about moisture content in oil impregnated paper is essential when estimating remaining life time of such system. A scaled down transformer insulation model was developed to gain wide experiences of on-site measurements of moisture content using dielectric response method. In order to provide reliable diagnostics of HV transformer insulation, various aspects like sensitivity of dielectric response to oil quality (oil conductivity and tandelta) etc. are discussed that may benefits the utilities and the service providers while using this technique. An investigation of moisture content on different parts of the insulation on a scaled down transformer model is performed using chemical analysis. Variation in the moisture content measured by FDS technique and Chemical method are also presented. The causes of variation in the results are analyzed.
  • Keywords
    dielectric properties; frequency-domain analysis; moisture; power transformer insulation; reliability; transformer oil; Chemical method; FDS technique; HV transformer insulation; chemical analysis; composite oil/cellulose insulation system; dielectric response measurement; moisture content; oil impregnated paper; oil quality; power transformer; service providers; transformer insulation system; Aging; Dielectric measurements; Dielectrics and electrical insulation; Frequency domain analysis; Frequency measurement; Moisture measurement; Oil insulation; Petroleum; Power transformer insulation; Power transformers; Composite insulation system; Dielectric response method; Moisture; Transformer;
  • fLanguage
    English
  • Publisher
    ieee
  • Conference_Titel
    Condition Monitoring and Diagnosis, 2008. CMD 2008. International Conference on
  • Conference_Location
    Beijing
  • Print_ISBN
    978-1-4244-1621-9
  • Electronic_ISBN
    978-1-4244-1622-6
  • Type

    conf

  • DOI
    10.1109/CMD.2008.4580432
  • Filename
    4580432