DocumentCode
2321855
Title
Overvoltages on distribution systems
Author
Du, S. Lam ; Tran-Quoc, T. ; Huy, H. Vo V ; Nguyen-Boi, K. ; Nguyen, Q.
Author_Institution
HCM City Electr. Co., Viet Nam
Volume
1
fYear
1998
fDate
18-21 Aug 1998
Firstpage
246
Abstract
In the framework of live working in a MV network, a cable-transformer system can be switched-off or switched-on. The ferroresonance phenomenon can occur during this procedure with very dangerous overvoltages. The metal oxide varistor (MOV) can fail during this phenomenon. The paper investigates the determination of the critical feeder length of cable, which will damage MOVs. A transformer model taking into account both the saturation and the hysteresis is proposed. The digital simulation concerning de-energization of the real configuration of the cable-transformer system is studied and the results obtained are verified by field tests
Keywords
arresters; ferroresonance; overvoltage protection; power cables; power distribution protection; power transformers; varistors; MV network; cable-transformer system; critical feeder cable length; de-energization; digital simulation; distribution system overvoltages; ferroresonance phenomenon; hysteresis; metal oxide varistor; surge arrester; transformer model; Arresters; Circuit breakers; Circuit faults; Cities and towns; Ferroresonance; Power cables; Power transformers; Saturation magnetization; Surges; Switching circuits;
fLanguage
English
Publisher
ieee
Conference_Titel
Power System Technology, 1998. Proceedings. POWERCON '98. 1998 International Conference on
Conference_Location
Beijing
Print_ISBN
0-7803-4754-4
Type
conf
DOI
10.1109/ICPST.1998.728963
Filename
728963
Link To Document