• DocumentCode
    2322201
  • Title

    Online partial discharge detection in HV cables using conventional current transformers

  • Author

    Mohamed, F.P. ; Siew, W.H. ; Li, Q.M.

  • Author_Institution
    Univ. of Strathclyde, Glasgow
  • fYear
    2008
  • fDate
    21-24 April 2008
  • Firstpage
    1250
  • Lastpage
    1253
  • Abstract
    This paper investigates the performance of conventional current transformer for online partial discharge detection in high voltage cables. It is based on the frequency response of such current transformers. The frequency behaviour was investigated using a simulation package (Powersim) by varying parameters including core permeability, stray capacitance, core material etc. Experimental investigation was also conducted on a 33 KV 200/5A current transformer. Simulation and experimental results are presented and compared in this paper.
  • Keywords
    current transformers; frequency response; partial discharge measurement; power cables; power engineering computing; power transformers; Powersim; conventional current transformers; core material; core permeability; frequency response; high voltage cable; online partial discharge detection; simulation package; stray capacitance; Cables; Costs; Crystalline materials; Current transformers; Frequency response; Partial discharges; Permeability; Power transformer insulation; Soft magnetic materials; Transformer cores; Current transformers; Frequency response; Partial discharges;
  • fLanguage
    English
  • Publisher
    ieee
  • Conference_Titel
    Condition Monitoring and Diagnosis, 2008. CMD 2008. International Conference on
  • Conference_Location
    Beijing
  • Print_ISBN
    978-1-4244-1621-9
  • Electronic_ISBN
    978-1-4244-1622-6
  • Type

    conf

  • DOI
    10.1109/CMD.2008.4580515
  • Filename
    4580515