Abstract
In this paper, detailed stress analysis and calculations on generator stator bars are presented. It points out that the electromagnetic force applied on the stator winding is confirmed as a 100 Hz alternative force. When the intrinsic frequency of the stator bars is equal or is close to 100 Hz, resonance of stator bars will occur. This resonance will cause serious damage to stator insulation. For serious vibrating conditions, this can lead to generator accidents such as internal short circuits or broken stator bars. Examples of stator end winding accidents which are caused by resonance frequency at 100 Hz are also presented and analyzed in the paper. A measuring method of stator bars intrinsic resonance frequency at 100 Hz is also introduced
Keywords
electric generators; electromagnetic forces; insulation testing; machine insulation; machine testing; stators; vibration measurement; wear testing; 100 Hz; broken stator bars; electromagnetic force; generator stator end windings; insulation wear protection; internal short circuits; mechanical resonance; stress analysis; vibration measurement; Accidents; Circuits; Electromagnetic forces; Insulation; Resonance; Resonant frequency; Stator bars; Stator windings; Stress; Vibration measurement;
fLanguage
English
Publisher
ieee
Conference_Titel
Power System Technology, 1998. Proceedings. POWERCON '98. 1998 International Conference on
Conference_Location
Beijing
Print_ISBN
0-7803-4754-4
Type
conf
DOI
10.1109/ICPST.1998.729239
Filename
729239
Link To Document