Single-phase auto-reclosing of the Vietnam 500 kV system
Author :
Tran-Quoc, T. ; Huy, H. Vo V ; Lan, H. Duong ; Nguyen-T.-Hoang, L. ; Dinh, L. Tran
Author_Institution :
Lab. d´´Electrotech. de Grenoble, Saint Martin d´´Heres, France
Volume :
2
fYear :
1998
fDate :
18-21 Aug 1998
Firstpage :
1077
Abstract :
The paper presents a study of single-phase auto-reclosing of the Vietnam 500 kV transmission system. The success of the single-phase auto-reclosing depends on the extinction of the secondary arc. Therefore, the influence of several factors such as shunt and neutral reactors, faulted phase and location, capacitive and inductive couplings and series capacitor discharge on the extinction of the secondary arc is investigated. The paper presents the influence of single-phase auto-reclosing on the transient stability of the Vietnamese power system. Finally, methods to increase the success of the single-phase auto-reclosing scheme also are investigated
Keywords :
circuit-breaking arcs; power system transient stability; power transmission protection; transmission networks; 500 kV; capacitive couplings; fault location; faulted phase; inductive couplings; neutral reactors; secondary arc extinction; series capacitor discharge; shunt reactors; single-phase auto-reclosing; transient stability; transmission system protection; Capacitors; Cities and towns; Couplings; Inductors; Power generation; Power system stability; Power system transients; Power transmission lines; Shunt (electrical); Zero voltage switching;
fLanguage :
English
Publisher :
ieee
Conference_Titel :
Power System Technology, 1998. Proceedings. POWERCON '98. 1998 International Conference on
Conference_Location :
Beijing
Print_ISBN :
0-7803-4754-4
Type :
conf
DOI :
10.1109/ICPST.1998.729251
Filename :
729251
Link To Document :
بازگشت