Title :
Shielding failure analysis of 132 kV transmission line shielded by surge arresters associated with multiple strokes lightning
Author :
Caulker, David ; Ahmad, Hussein ; Malek, Zulkurnain Abdul ; Yusof, Sallehhudin
Author_Institution :
Inst. of High Voltage & High Current, Univ. Teknol. Malaysia, Johor Bahru, Malaysia
Abstract :
Analysis of shielding failure is carried out to observe flashover of insulators parallel with phase conductors of a transmission line associated with a lightning strike on phase conductor. Peak current of different magnitude have been used to represent the multiple strokes lightning (MSL). This paper aims to simulate the worst case due to transmission shielding failure with three direct strikes to a line phase conductor of magnitudes 25 kA, 35 kA, 50 kA, 65 kA and 80 kA per strike respectively. Insulators where flashover had occurred with respect to MSL were identified. Installation of an arrester on a phase insulator where a flashover has occurred proven to be useful mitigation technique thatch could prevent flashover of the insulator and also improves lighting performance of the line.
Keywords :
arresters; failure analysis; flashover; lightning protection; power transmission lines; power transmission protection; power transmission reliability; shielding; flashover; lighting performance; multiple strokes lightning; phase conductor; phase insulator; shielding failure analysis; surge arrester; transmission line; transmission shielding failure; voltage 132 V; Flashover; Insulators; Multiple strokes; Phase conductors; Shielding Failure; Strokes; Surge Arresters; Transmission line;
Conference_Titel :
Electrical and Computer Engineering (ICECE), 2010 International Conference on
Conference_Location :
Dhaka
Print_ISBN :
978-1-4244-6277-3
DOI :
10.1109/ICELCE.2010.5700687