• DocumentCode
    2346413
  • Title

    Impact of STATCOM modeling on its effect on distance relay tripping characteristic

  • Author

    Kazemi, A. ; Jamali, S. ; Shateri, H.

  • Author_Institution
    Iran Univ. of Sci. & Technol., Tehran
  • fYear
    2008
  • fDate
    3-5 June 2008
  • Firstpage
    1746
  • Lastpage
    1751
  • Abstract
    This paper presents the measured impedance at the relaying point in the presence of STATic synchronous COMpensator (STATCOM), in the case of two different models for STATCOM. The presence of STATCOM on a transmission line greatly affects the measured impedance at the relaying point. The measured impedance itself depends on the power system structural conditions, pre-fault conditions, and especially the ground fault resistance. In the presence of STATCOM, its structural and controlling parameters as well as its installation position affects the tripping characteristic. Here, the measured impedance at the relaying point is calculated due to the mentioned affecting parameters, including the selected model for STATCOM.
  • Keywords
    power system simulation; static VAr compensators; STATCOM modeling; distance relay tripping; ground fault resistance; power system structural conditions; pre-fault conditions; static synchronous compensator; transmission line; Automatic voltage control; Electrical resistance measurement; Impedance measurement; Power measurement; Power system faults; Power system modeling; Power system relaying; Power transmission lines; Protective relaying; Transmission line measurements;
  • fLanguage
    English
  • Publisher
    ieee
  • Conference_Titel
    Industrial Electronics and Applications, 2008. ICIEA 2008. 3rd IEEE Conference on
  • Conference_Location
    Singapore
  • Print_ISBN
    978-1-4244-1717-9
  • Electronic_ISBN
    978-1-4244-1718-6
  • Type

    conf

  • DOI
    10.1109/ICIEA.2008.4582819
  • Filename
    4582819