• DocumentCode
    2352271
  • Title

    PD pulse propagation in shielded power cable for symmetric and asymmetric PD pulses

  • Author

    Oussalah, Naima ; Zebboudj, Youcef ; Boggs, Steven

  • Author_Institution
    High Voltage Lab., Univ. A.M. of Bejaia
  • fYear
    2006
  • fDate
    11-14 June 2006
  • Firstpage
    30
  • Lastpage
    33
  • Abstract
    Partial discharge is a useful diagnostic method for a wide range of power apparatus. In the case of shielded power cable, partial discharge can detect workmanship-induced defects in accessories, as well as cavities and electrical trees in the dielectric. Shielded power cables can be considered lossy transmission lines. The high frequency attenuation of the cable causes the peak amplitude of a PD pulse, as well as the pulse energy, to decrease as a function of distance propagated. We develop analytical expressions which characterize the PD pulse propagation in a typical shielded power cable for both symmetric and asymmetric PD pulses for an attenuation constant which increases linearly with frequency, as is normally the case for shielded solid dielectric power cable
  • Keywords
    cable shielding; partial discharge measurement; power cable insulation; trees (electrical); PD pulse propagation; cable accessories; defect detection; diagnostic method; electrical trees; high frequency attenuation; lossy transmission line; partial discharge; power apparatus; power cable shielding; solid dielectric; Attenuation measurement; Bandwidth; Equations; Fourier transforms; Materials science and technology; Partial discharges; Physics; Power cables; Space vector pulse width modulation; Voltage;
  • fLanguage
    English
  • Publisher
    ieee
  • Conference_Titel
    Electrical Insulation, 2006. Conference Record of the 2006 IEEE International Symposium on
  • Conference_Location
    Toronto, Ont.
  • ISSN
    1089-084X
  • Print_ISBN
    1-4244-0333-2
  • Type

    conf

  • DOI
    10.1109/ELINSL.2006.1665250
  • Filename
    1665250