• DocumentCode
    2352555
  • Title

    High speed catastrophic events in technical insulating liquids

  • Author

    Jaksts, Albert ; Blanchet, Guilhem

  • Author_Institution
    Corporate Res., ABB AB, Vasteras
  • fYear
    2006
  • fDate
    11-14 June 2006
  • Firstpage
    85
  • Lastpage
    88
  • Abstract
    As liquid breakdown modeling is still in its infancy, dielectric breakdown tests remain one source of input regarding the design of an insulation system for power apparatus. The relevance of small scale tests has long been known to be limited. It is known that designers would never dare to use the strengths seen in such tests. The paper argues that one aspect that may describe the reason for the discrepancy is that the physics controlling the breakdown are different for the small scale tests when comparing to the breakdowns observed in large technical insulation systems. Experimental data are presented showing that catastrophic events of technical interest arise in different liquids at different voltage levels. Voltage differences obtained with the impulse overvoltage method are not seen when ´traditional´ small scale breakdown tests are performed
  • Keywords
    dielectric liquids; electric breakdown; insulation testing; power apparatus; breakdown modeling; catastrophic event; dielectric breakdown test; impulse overvoltage method; insulating liquid; insulation system design; power apparatus; Breakdown voltage; Control systems; Dielectric breakdown; Dielectric liquids; Dielectrics and electrical insulation; Electric breakdown; Insulation testing; Physics; Power system modeling; System testing;
  • fLanguage
    English
  • Publisher
    ieee
  • Conference_Titel
    Electrical Insulation, 2006. Conference Record of the 2006 IEEE International Symposium on
  • Conference_Location
    Toronto, Ont.
  • ISSN
    1089-084X
  • Print_ISBN
    1-4244-0333-2
  • Type

    conf

  • DOI
    10.1109/ELINSL.2006.1665263
  • Filename
    1665263