• DocumentCode
    2356982
  • Title

    Partial discharge behaviour of an alternative insulating liquid compared to mineral oil

  • Author

    Eberhardt, R. ; Muhr, H.M. ; Lick, W. ; Wieser, B. ; Schwarz, R. ; Pukel, G.

  • Author_Institution
    Dept. of High Voltage Eng. & Syst. Manage., Graz Univ. of Technol., Graz, Austria
  • fYear
    2010
  • fDate
    23-27 May 2010
  • Firstpage
    426
  • Lastpage
    429
  • Abstract
    In times when personal safety and the security of electrical power supply become more and more important, the usage of alternative insulation fluids is demanded in large power transformers. The minimizing of fire loads is another significant reason for new liquids. Different companies are offering such alternative insulation liquids which are already used in distribution transformers. On the other hand there is little experience with those fluids in large power transformers. For the confirmation of the usability of new insulating liquids comparison methods must be tested to find the differences between the alternative insulating fluids and commonly used mineral oil. There are different methods for characterising insulating materials, like AC-Breakdown tests, partial discharge tests, lightning and switching impulse voltage tests, etcetera. Partial discharge behaviour is a distinguishing characteristic of an insulating medium. This paper shows the partial discharge behaviour of alternative insulation liquids such as synthetic and natural esters, compared to commonly used mineral oil. To generate the PD patterns, voltages up to 30kV and inhomogeneous test arrangements were used. A model of an oil/board insulation system was created by using sheets of pressboard.
  • Keywords
    impulse testing; insulating materials; partial discharges; power transformers; distribution transformer; electrical power supply security; mineral oil; partial discharge behaviour; personal safety; power transformer; switching impulse voltage test; Dielectric liquids; Fluids; Minerals; Oil insulation; Partial discharges; Power transformer insulation; Alternative liquids; Oil; Partial Discharge; Transformer; ester;
  • fLanguage
    English
  • Publisher
    ieee
  • Conference_Titel
    Power Modulator and High Voltage Conference (IPMHVC), 2010 IEEE International
  • Conference_Location
    Atlanta, GA
  • Print_ISBN
    978-1-4244-7131-7
  • Type

    conf

  • DOI
    10.1109/IPMHVC.2010.5958385
  • Filename
    5958385