• DocumentCode
    2357931
  • Title

    Test results on a thermo-syphon concept to high-power cool desktop computers and servers

  • Author

    Webb, R.L.

  • Author_Institution
    Pennsylvania State Univ., University Park, PA, USA
  • fYear
    2002
  • fDate
    12-14 March 2002
  • Firstpage
    151
  • Lastpage
    158
  • Abstract
    This paper reports measured thermal performance of two prototype thermo-syphon devices designed to cool desktop computers and servers. The prototype was designed to reject 100 W with 35 K CPU-to-air temperature difference using an 80 mm 3350 rpm fan for air flow. One prototype is aluminum and uses R-134A, while the other is copper and uses water. The working fluid boils at the CPU and is condensed in tubes of an air-cooled heat exchanger, based on automotive technology. The frontal areas of the heat exchangers are 97 /spl times/ 70 mm (aluminum) and 54 /spl times/ 70 mm (copper). The thermo-syphon device uses high-performance heat transfer technology, consisting of louvre fins (air-cooled unit), and a sintered boiling surface. The experimental results of the aluminum/R-134A prototype are in good agreement with the previously published predicted thermal resistance. The performance of the prototype systems are believed to provide the highest performance of any published air-cooled heat rejection system.
  • Keywords
    boiling; cooling; thermal management (packaging); thermal resistance; 100 W; CPU-to-air temperature difference; air-cooled heat exchanger; air-cooled heat rejection system; desktop computers; fan; louvre fins; servers; sintered boiling surface; thermal performance; thermal resistance; thermo-syphon concept; Aluminum; Automotive engineering; Central Processing Unit; Copper; Heat transfer; Prototypes; Surface resistance; Temperature; Testing; Thermal resistance;
  • fLanguage
    English
  • Publisher
    ieee
  • Conference_Titel
    Semiconductor Thermal Measurement and Management, 2002. Eighteenth Annual IEEE Symposium
  • Conference_Location
    San Jose, CA, USA
  • ISSN
    1065-2221
  • Print_ISBN
    0-7803-7327-8
  • Type

    conf

  • DOI
    10.1109/STHERM.2002.991361
  • Filename
    991361