Title :
Research on calibration methods for pulse resistive divider
Author :
Shuai Wang ; Jing Wu ; Haiming Shao
Author_Institution :
Beihang Univ., Beijing, China
Abstract :
There are two methods commonly used for the performance test of voltage divider system. Step response method is used to measure the transient response of system, and frequency response method is used to measure the amplitude-frequency characteristics and phase-frequency characteristics. This paper discusses the equivalent conversion relationship of the characteristic parameters of time-domain and frequency-domain. On this basis, the calibration of pulse resistor divider has been studied. Comparative experiment results show these calibration methods have good accuracy and consistency. The frequency range of divider can be achieved from the time-domain response curves, and self-calibration can be accomplished.
Keywords :
calibration; electric resistance measurement; frequency-domain analysis; pulse measurement; resistors; time-domain analysis; voltage dividers; voltage measurement; amplitude-frequency measurement; calibration method; equivalent conversion relationship; frequency response measurement; frequency-domain parameter; phase-frequency measurement; pulse resistive voltage divider system; step response method; time-domain parameter; transient response measurement; voltage measurement; Calibration; Frequency conversion; Frequency-domain analysis; Impedance; Impedance measurement; Time-domain analysis; Voltage divider; calibration; frequency-domain; network; time-domain;
Conference_Titel :
Precision Electromagnetic Measurements (CPEM 2014), 2014 Conference on
Conference_Location :
Rio de Janeiro
Print_ISBN :
978-1-4799-5205-2
DOI :
10.1109/CPEM.2014.6898231