DocumentCode :
2360094
Title :
Efficiency comparison of voltage source and current source drive system for medium voltage applications
Author :
Suh, Yongsug ; Steinke, Juergen ; Steimer, Peter
Author_Institution :
ABB Switzerland Ltd., Turgi
fYear :
2005
fDate :
11-14 Sept. 2005
Abstract :
This paper calculates and compares the efficiency and loss distribution in three most popular state-of-the-art types of medium voltage drive systems; current source drive with active front-end rectifier, current source drive with 18-pulse thyristor rectifier, and three-level voltage source drive with 12-pulse/24-pulse diode rectifier. Based on the proposed simple and accurate method of calculating switching losses, snubber and filter losses, three-level voltage source drive system has been found to produce the highest efficiency of 98.77% under the rated load of 1.6 MW
Keywords :
diodes; electric drives; power filters; rectifying circuits; snubbers; switching convertors; thyristor applications; 1.6 MW; 18-pulse thyristor rectifier; active front-end rectifier; current source drive; current source drive system; diode rectifier; filter losses; loss distribution; medium voltage applications; snubbers; switching losses; three-level voltage source drive; three-level voltage source drive system; voltage drive systems; voltage source; Drives; Filters; Inverters; Loss measurement; Medium voltage; Power system reliability; Rectifiers; Switching converters; Switching loss; Thyristors; AC machine; Current source inverter; Efficiency; Multilevel converters; Voltage source inverters;
fLanguage :
English
Publisher :
ieee
Conference_Titel :
Power Electronics and Applications, 2005 European Conference on
Conference_Location :
Dresden
Print_ISBN :
90-75815-09-3
Type :
conf
DOI :
10.1109/EPE.2005.219486
Filename :
1665676
Link To Document :
بازگشت