• DocumentCode
    2363297
  • Title

    Influence of Long High Voltage Cables on Total Harmonic Distortion of Currents in Wind Farms

  • Author

    Plotkin, Juriy ; Schulz, Detlef ; Hanitsch, Rolf

  • Author_Institution
    Berlin Univ. of Technol.
  • fYear
    2006
  • fDate
    6-10 Nov. 2006
  • Firstpage
    3189
  • Lastpage
    3194
  • Abstract
    Harmonic production of a 132 MW on-land wind park is investigated. It is shown, that the main reason for current harmonics is the earth capacitance of a long high-voltage cable, which forms a small impedance for grid-specific voltage harmonics and causes harmonic current flow from the grid into the wind park. Measurements confirm the theoretical approach
  • Keywords
    harmonic distortion; power cables; power grids; wind power plants; 132 MW; earth capacitance; grid-specific voltage harmonics; high-voltage cables; onland wind park; total harmonic distortion; wind farms; Cables; Impedance; Induction generators; Power measurement; Power transmission lines; Production; Total harmonic distortion; Voltage; Wind energy; Wind farms;
  • fLanguage
    English
  • Publisher
    ieee
  • Conference_Titel
    IEEE Industrial Electronics, IECON 2006 - 32nd Annual Conference on
  • Conference_Location
    Paris
  • ISSN
    1553-572X
  • Print_ISBN
    1-4244-0390-1
  • Type

    conf

  • DOI
    10.1109/IECON.2006.347479
  • Filename