• DocumentCode
    236332
  • Title

    A reference system for on-site calibration of high-voltage revenue metering systems

  • Author

    Rietveld, Gert ; Fransen, Martin ; Blanc, Nicolas ; Houtzager, Ernest ; So, Eddy

  • Author_Institution
    VSL, Delft, Netherlands
  • fYear
    2014
  • fDate
    24-29 Aug. 2014
  • Firstpage
    404
  • Lastpage
    405
  • Abstract
    A reference system for on-site calibration and validation of revenue metering systems is realized. The system consists of a three-phase power meter and high-accuracy current and voltage transformers (CTs and VTs). Measurements can be made up to 150 kV (system voltage) and line currents up to 5000 A. The power meter, the CTs, and the VTs were all calibrated. Based on the excellent results of the calibration of these components it is possible to predict the full system performance with an uncertainty of less than 100 μW/VA. This estimation was verified with a full system validation, showing that the system is much more accurate than required and that detrimental effects to the accuracy are well understood.
  • Keywords
    calibration; current transformers; metering; potential transformers; power meters; reference circuits; full system validation; high-accuracy current transformers; high-accuracy voltage transformers; high-voltage revenue metering systems; on-site calibration; reference system; three-phase power meter; Accuracy; Calibration; Current measurement; Power measurement; Substations; Uncertainty; Voltage measurement; billing; current transformer; high current; high voltage (HV); power; power meter; precision measurements; revenue metering; substation; traceability; voltage transformer;
  • fLanguage
    English
  • Publisher
    ieee
  • Conference_Titel
    Precision Electromagnetic Measurements (CPEM 2014), 2014 Conference on
  • Conference_Location
    Rio de Janeiro
  • ISSN
    0589-1485
  • Print_ISBN
    978-1-4799-5205-2
  • Type

    conf

  • DOI
    10.1109/CPEM.2014.6898430
  • Filename
    6898430