DocumentCode :
2364510
Title :
Research on a Practical Approach of Integrated Compensation for Unbalanced Load
Author :
Zhengpai, Cui ; Han, Yu ; Sheng, Li ; Yunbo, Long ; Jianhua, Zhang
Author_Institution :
Key Lab. of Power Syst. Protection & Dynamic Security Monitoring & Control, North China Electr. Power Univ., Beijing
fYear :
2006
fDate :
6-10 Nov. 2006
Firstpage :
2672
Lastpage :
2676
Abstract :
Asymmetric load is quite common in distribution network, the compensation of which is a serious problem under some situations. A novel integrated compensation method is put forward based on the principle of reactive power compensation. A practical formula of the balancing compensation for the unbalanced load is deduced by using the symmetrical component method, which is not only suitable for the three-phase three-wire system but also for the three-phase four-wire system. The simulation results based on MATLAB show the validity of the compensation for the unbalanced load with different connection, and verify the correctness of theoretical deduction
Keywords :
compensation; distribution networks; load (electric); reactive power; MATLAB; asymmetric load; balancing compensation; distribution network; integrated compensation; reactive power compensation; symmetrical component method; three-phase four-wire system; three-phase three-wire system; unbalanced load; Admittance; Control systems; Laboratories; Monitoring; Power system dynamics; Power system protection; Power system security; Reactive power; Reactive power control; Voltage;
fLanguage :
English
Publisher :
ieee
Conference_Titel :
IEEE Industrial Electronics, IECON 2006 - 32nd Annual Conference on
Conference_Location :
Paris
ISSN :
1553-572X
Print_ISBN :
1-4244-0390-1
Type :
conf
DOI :
10.1109/IECON.2006.347577
Filename :
4153031
Link To Document :