    Effect of mobile conducting particles on the electrical strength of the insulation system of SF6 insulated switchgear

  • Author

    Labus-Nawrat, K. ; Grzybowski, S.

  • Author_Institution
    Inst. for Electrotech., Warsaw, Poland
  • fYear
    1989
  • fDate
    29 Oct-2 Nov 1989
  • Firstpage
    483
  • Lastpage
    488
  • Abstract
    The authors present data obtained from tests conducted on an SF 6 GIS (gas-insulated switchgear) model, 123 kV, having coaxial cylinders of 240/80-mm diameter in the presence of mobile particles. In the case of a vertical GIS construction and in the presence of conducting particles, a great hazard to the insulation is shown to occur when overvoltages appear in service. There is a wide range of imminent particles since heavy and light particles are included. The presence of conducting particles in the case of a conic spacer insulator also causes a hazard to insulation due to overvoltages appearing in service. The detection of particles left after final assembly on site and of those located on the spacer insulators which were tested in 123-kV GIS is possible using tests with applied 185 kV AC voltage and tests with impulse voltage at 80% basic insulation level
  • Keywords
    electric strength; gaseous insulation; insulation testing; overvoltage; sulphur compounds; switchgear protection; 123 kV; SF6 insulated switchgear; conic spacer insulator; electrical strength; gaseous SF6 insulation; mobile conducting particles; model tests; overvoltages; Coaxial components; Gas insulation; Geographic Information Systems; Hazards; Impulse testing; Insulation testing; Insulator testing; Surges; Switchgear; Voltage;
  • fLanguage
    English
  • Publisher
    ieee
  • Conference_Titel
    Electrical Insulation and Dielectric Phenomena, 1989. Annual Report., Conference on
  • Conference_Location
    Leesburg, VA
  • Type

    conf

  • DOI
    10.1109/CEIDP.1989.69593
  • Filename
    69593