  • Abstract
    With steady increase in the wind power penetration, regulatory standards for grid connection have evolved. The regulatory standards require the wind generation system to ride-through disturbances such as faults and support the grid during such events. This fault ride-through capability is determined by its corresponding critical clearing time (CCT). Conventionally, determination of CCT involves a large number of trial and error iterations that requires repetitive runs of related time-domain simulations. A method is proposed in this paper to compute CCT using non-conventional approach that avoids running related time-domain simulations several times. This work proposes a method to enhance the fault- ride through capability of squirrel cage induction generator based wind farms using Dynamic Voltage Regulator (DVR). The DVR controller is designed to work under fault conditions, which improves the critical clearing time of the system by injecting real power required by the system. The detailed simulation results are presented.
  • Keywords
    asynchronous generators; power generation control; power generation faults; power grids; time-domain analysis; voltage regulators; wind power plants; CCT determination; DVR; DVR controller; critical clearing time; dynamic voltage regulator; fault ride-through capability; grid connected squirrel cage induction generator; nonconventional approach; regulatory standards; ride-through disturbances; time-domain simulations; wind farms; wind generation system; Circuit faults; Induction generators; Power transmission lines; Rotors; Stators; Voltage control; Critical Clearing Time (CCT); Critical Speed; Dynamic Voltage Restorer (DVR); Fault-Ride Through (FRT) Capability; Squirrel Cage Induction Generator (SCIG);
  • fLanguage
    English
  • Publisher
    ieee
  • Conference_Titel
    Environment and Electrical Engineering (EEEIC), 2012 11th International Conference on
  • Conference_Location
    Venice
  • Print_ISBN
    978-1-4577-1830-4
  • Type

    conf

  • DOI
    10.1109/EEEIC.2012.6221432
  • Filename
    6221432