DocumentCode :
23677
Title :
Minimum switching loss pulse width modulation for reduced power conversion loss in reactive power compensators
Author :
Siva Prasad, Jaldanki ; Narayanan, G.
Author_Institution :
Dept. of Electr. Eng., Indian Inst. of Sci., Bangalore, India
Volume :
7
Issue :
3
fYear :
2014
fDate :
Mar-14
Firstpage :
545
Lastpage :
551
Abstract :
Advanced bus-clamping switching sequences, which employ an active vector twice in a subcycle, are used to reduce line current distortion and switching loss in a space vector modulated voltage source converter. This study evaluates minimum switching loss pulse width modulation (MSLPWM), which is a combination of such sequences, for static reactive power compensator (STATCOM) application. It is shown that MSLPWM results in a significant reduction in device loss over conventional space vector pulse width modulation. Experimental verification is presented at different power levels of up to 150 kVA.
Keywords :
PWM power convertors; static VAr compensators; MSLPWM; STATCOM application; active vector; advanced bus-clamping switching sequences; current distortion; minimum switching loss pulse width modulation; reactive power compensators; reduced power conversion loss; space vector modulated voltage source converter; static reactive power compensator application; switching loss;
fLanguage :
English
Journal_Title :
Power Electronics, IET
Publisher :
iet
ISSN :
1755-4535
Type :
jour
DOI :
10.1049/iet-pel.2013.0299
Filename :
6759660
Link To Document :
بازگشت