DocumentCode :
2367968
Title :
Simulation of a `direct on line´ start of a large induction motor connected to a salient pole synchronous generator
Author :
Tuinman, E. ; Piers, P. ; de Weerdt, R.
Author_Institution :
HMA Power Syst. BV, Netherlands
fYear :
1998
fDate :
30 Sep-2 Oct 1998
Firstpage :
362
Lastpage :
367
Abstract :
The paper describes the transient behaviour of a synchronous generator when a large induction motor is switched direct on line. The influence of the AVR (Automatic Voltage Regulator), the damper winding parameters and the pre-load of the generator are described. Comparison is made with analytical formulae for calculating voltage drops at sudden load increase. The simulations in the time domain are performed using the flux linkages of generator and motor as state space variables. The AVR and equations of motion (for motor and generator) are described as a set of first order differential equations
Keywords :
induction motors; AVR; Automatic Voltage Regulator; analytical formulae; damper winding parameters; direct on line; equations of motion; first order differential equations; flux linkages; large induction motor simulation; pre-load; salient pole synchronous generator; state space variables; sudden load increase; time domain simulation; transient behaviour; voltage drops;
fLanguage :
English
Publisher :
iet
Conference_Titel :
Simulation '98. International Conference on (Conf. Publ. No. 457)
Conference_Location :
York
ISSN :
0537-9989
Print_ISBN :
0-85296-709-8
Type :
conf
DOI :
10.1049/cp:19980664
Filename :
731876