DocumentCode
2368800
Title
Harmonic performance systems (SFC) for commissioning of 200MVA generators
Author
Arash, Mohammad Ali ; Ezoji, Hadi ; Alborzi, Mohmmad Hossein ; Ghasemnia, Reza Farid ; Doborji, Ashraf Maleki
Author_Institution
Mapna Electr. & Control Eng., MAPNAEC, Karaj, Iran
fYear
2012
fDate
18-25 May 2012
Firstpage
1000
Lastpage
1005
Abstract
During trigging of Gas generators in Aliabad power plant by trigger system (SFC made by ABB company), the generated current harmonic during trigging causes negative impacts on voltage of local power distribution network, this problem caused Flicker on lighting system of administrative units. In order to clarify the problem, the current samples at different operating frequencies of generator were recorded from feeding bus of the trigger system. By examining these figures it was determined that the value of the fifth harmonic produced by the trigger system is higher than standard value. To resolve these issues appropriate solutions were proposed.
Keywords
distribution networks; electric generators; gas turbine power stations; power system harmonics; SFC; current harmonics; feeding bus; flicker; gas turbine power plant; harmonic performance systems; lighting system; local power distribution network; trigger system; trigging causes; Bridge circuits; Generators; Harmonic analysis; Power generation; Rectifiers; Standards; Thyristors; Flicker; harmonic; normal mode; pulse mode; stimulation system (SEE); trigger system (SFC);
fLanguage
English
Publisher
ieee
Conference_Titel
Environment and Electrical Engineering (EEEIC), 2012 11th International Conference on
Conference_Location
Venice
Print_ISBN
978-1-4577-1830-4
Type
conf
DOI
10.1109/EEEIC.2012.6221524
Filename
6221524