• DocumentCode
    2372435
  • Title

    Design and application of low ratio high accuracy split-core, core-balance current transformer

  • Author

    Das, J.C. ; Mullikin, Randy

  • Author_Institution
    AMEC, Inc., Atlanta, GA
  • fYear
    2008
  • fDate
    22-27 June 2008
  • Firstpage
    192
  • Lastpage
    201
  • Abstract
    The paper describes the design and application of a split-core CT of large dimensions, specifically designed for mounting in 13.8 kV switchgear cubical on the phase bus bars. Though split-core CTpsilas of high current ratio are available, the authors believe that the core-balance CT described in this paper is unique, as no similar CT was readily available in the US/European market. Thus, there is no equivalent installation in the industry of the specifications described in the paper. The CT discussed in this paper was specifically designed to meet the requirements of dimensions and accuracy for sensitive ground fault and directional ground fault relaying.
  • Keywords
    busbars; current transformers; fault diagnosis; power transformer protection; relay protection; switchgear; transformer cores; European market; core-balance current transformer; directional ground fault relaying; ground fault sensitivity; low ratio high accuracy split-core; phase bus bars; switchgear; voltage 13.8 kV; Bars; Cables; Circuit faults; Circuit testing; Current transformers; Magnetic cores; Relays; Switchgear; Thermal resistance; Transformer cores; CT saturation; Split-core; class C and T accuracies; core-balance current; transformers;
  • fLanguage
    English
  • Publisher
    ieee
  • Conference_Titel
    Pulp and Paper Industry Technical Conference, 2008. PPIC 2008. Conference Record of 2008 54th Annual
  • Conference_Location
    Seattle, WA
  • ISSN
    0190-2172
  • Print_ISBN
    978-1-4244-2524-2
  • Electronic_ISBN
    0190-2172
  • Type

    conf

  • DOI
    10.1109/PAPCON.2008.4585808
  • Filename
    4585808