DocumentCode
2373860
Title
Searching method of grounding route in buildings using amplitude and phase
Author
Kuramoto, Shoichi ; Hattori, Mitsuo ; Ideguchi, Tsuyoshi
Author_Institution
NTT Multimedia Networks Labs., Tokyo, Japan
fYear
1997
fDate
18-22 Aug 1997
Firstpage
149
Lastpage
153
Abstract
Grounding systems must be maintained to protect equipment from lightning surges and other unintentional overvoltages occurring over power lines. However, in many cases it is difficult to maintain a reliability grounding system because unintended connections are sometimes made when connecting telecommunication lines between equipment, or when a cabinet accidentally comes into contact with the metal framework of the building. This paper describes a method of searching for the grounding route by using both amplitude and phase. The phase reference is also obtained from the injected signal, whose frequency is ten times that of the searching signal, so as to remove the reference line. The results indicate that this method can detect whether the observation point is connected directly or indirectly to the injection point
Keywords
earthing; lightning protection; phase measurement; reliability; surge protection; amplitude measurement; buildings; equipment protection; grounding route; injected signal; lightning surges; phase measurement; phase reference; reliability grounding system; searching method; telecommunication lines; unintended connections; Electromagnetic interference; Grounding; Integrated circuit reliability; Joining processes; Lightning; Maintenance; Phase detection; Phase measurement; Power system protection; Surge protection;
fLanguage
English
Publisher
ieee
Conference_Titel
Electromagnetic Compatibility, 1997. IEEE 1997 International Symposium on
Conference_Location
Austin, TX
Print_ISBN
0-7803-4140-6
Type
conf
DOI
10.1109/ISEMC.1997.667559
Filename
667559