Title :
Islanding tests near a mini hydro generating plant
Author :
Jutras, R. ; Lafond, C. ; Plamondon, M. ; Proulx, S. ; Srinivasan, K.
Author_Institution :
IREQ, Varennes, Que., Canada
fYear :
1997
fDate :
11-16 May 1997
Firstpage :
91
Lastpage :
95
Abstract :
In this paper, the authors present the measurements taken while a mini-hydroelectric power plant and the adjoining load were islanded on a 25 kV distribution feeder. This was as a part of the plant´s acceptance tests before commissioning. The frequency was allowed to vary from 56.3 to 64.5 Hz before the generation was tripped off. The authors also present the estimation of the moment of inertia of the generating system from these measurements
Keywords :
distribution networks; hydroelectric power stations; power system interconnection; power system measurement; 25 kV; 56.3 to 64.5 Hz; acceptance tests; commissioning; distribution feeder; generation tripping; mini-hydroelectric power plant; moment of inertia; power plant islanding tests; Frequency; Performance evaluation; Power generation; Power measurement; Power system modeling; Power system reliability; Power system stability; Power system transients; Testing; Voltage;