DocumentCode
2377290
Title
Flexible simultaneous feasibility test in energy market
Author
Zhu, Jizhong ; Cheung, Kwok
Author_Institution
AREVA T&D Inc., Redmond, WA, USA
fYear
2010
fDate
25-29 July 2010
Firstpage
1
Lastpage
7
Abstract
The simultaneous feasibility test (SFT) performs the network sensitivity analysis under the base case and contingency cases in power systems. This paper presents the practical implementation of the simultaneous feasibility test in the energy market. SFT calculation includes loss sensitivities and constraint shift factors either for E-nodes or P-nodes and the used reference is the distributed load reference. Several SFT modes are discussed in the paper. The schematic of data flow between SFT and other market system applications in a day-ahead market clearing process is also analyzed. Especially, the dead bus logic is proposed to compute the sensitivities for the open/dead node such as open unit. The calculating results based on PJM system are shown in the paper.
Keywords
load distribution; power markets; sensitivity analysis; PJM system; dead bus logic; distributed load reference; energy market; flexible simultaneous feasibility test; network sensitivity analysis; Standard market design; decoupled power flow; energy markets; locational marginal prices; loss sensitivity; market clearing engine; shift factor; simultaneous feasibility test; spot pricing;
fLanguage
English
Publisher
ieee
Conference_Titel
Power and Energy Society General Meeting, 2010 IEEE
Conference_Location
Minneapolis, MN
ISSN
1944-9925
Print_ISBN
978-1-4244-6549-1
Electronic_ISBN
1944-9925
Type
conf
DOI
10.1109/PES.2010.5589447
Filename
5589447
Link To Document