• DocumentCode
    2379613
  • Title

    Detection of minor winding deformation fault in high frequency range for power transformer

  • Author

    Tang, W.H. ; Shintemirov, A. ; Wu, Q.H.

  • Author_Institution
    Dept. of Electr. Eng. & Electron., Univ. of Liverpool, Liverpool, UK
  • fYear
    2010
  • fDate
    25-29 July 2010
  • Firstpage
    1
  • Lastpage
    6
  • Abstract
    This paper presents a simplified distributed parameter model for minor winding deformation fault analysis of power transformers on the basis of frequency response analysis (FRA). The FRA data of an experimental transformer is employed as a reference trace, which are compared with the simulations of the simplified distributed parameter model concerning minor winding deformation faults. In order to perform quantitative analysis when a deformation fault occurs, three statistical indicators are used to analyze the FRA simulation data. It is suggested in the results that minor winding deformation faults can be detected at the frequency range above 1 MHz.
  • Keywords
    deformation; fault diagnosis; frequency response; power transformers; statistical analysis; transformer windings; FRA simulation data; frequency response analysis; minor winding deformation fault detection analysis; power transformer; quantitative analysis; simplified distributed parameter model; statistical indicators; Circuit faults; Deformable models; Frequency measurement; Mathematical model; Power transformers; Transfer functions; Windings; Transformer winding; distortion fault; frequency response analysis;
  • fLanguage
    English
  • Publisher
    ieee
  • Conference_Titel
    Power and Energy Society General Meeting, 2010 IEEE
  • Conference_Location
    Providence, RI
  • ISSN
    1944-9925
  • Print_ISBN
    978-1-4244-6549-1
  • Electronic_ISBN
    1944-9925
  • Type

    conf

  • DOI
    10.1109/PES.2010.5589573
  • Filename