• DocumentCode
    2380214
  • Title

    The effect of DC offset on current operated relays

  • Author

    Stringer, Norman T.

  • Author_Institution
    Basler Electr. Co., Highland, IL, USA
  • fYear
    1997
  • fDate
    11-16 May 1997
  • Firstpage
    154
  • Lastpage
    159
  • Abstract
    When a fault occurs on a power system, one or more phases will experience DC offset. This DC component, which will decay dependent on the L/R time constant of the power system, can produce saturation in current transformers, as well as the input current transformers of the protective relays sensing the fault. In addition, when the fault current is interrupted, the resulting DC tail can maintain the current above the relay´s pickup setting for a time dependent on the CT secondary circuit L/R time constant. This paper discusses this phenomenon and how it can affect the operation of two types of current operated relays
  • Keywords
    current transformers; fault currents; power system protection; power system relaying; power transformer protection; relay protection; DC offset; DC tail; L/R time constant; current operated relays; current transformer saturation; power system protective relays; transformer secondary circuit; Circuit faults; Coils; Current transformers; Fault currents; Power system protection; Power system relaying; Protective relaying; Relays; Switches; Voltage;
  • fLanguage
    English
  • Publisher
    ieee
  • Conference_Titel
    Industrial and Commercial Power Systems Technical Conference, 1997. Conference Record, Papers Presented at the 1997 Annual Meeting., IEEE 1997
  • Conference_Location
    Philadelphia, PA
  • Print_ISBN
    0-7803-3825-1
  • Type

    conf

  • DOI
    10.1109/ICPS.1997.596025
  • Filename
    596025