Title
Distributed voltage control in AuRA-NMS
Author
Taylor, P.C. ; Xu, T. ; Wade, N.S. ; Prodanovic, M. ; Silversides, R. ; Green, T. ; Davidson, E.M. ; McArthur, S.
Author_Institution
Sch. of Eng. & Comput. Sci., Univ. of Durham, Durham, UK
fYear
2010
fDate
25-29 July 2010
Firstpage
1
Lastpage
7
Abstract
This paper presents real time test results arising from the application of a case based reasoning technique for voltage control of a section of existing UK 11kV network. The test network includes two distributed generation schemes. The objective of the case based reasoning technique is to maintain voltages within statutory limits while also maximizing the DG access to the network. The control algorithm is embedded on a commercially available hardware platform designed for installation in power system substations. The case based reasoning technique employs the following control actions to achieve its objectives: DG real power control, DG reactive power control and transformer tap change control. The voltage control technique is tested during over-voltage conditions and for situations where only partial sensor data is available.
Keywords
case-based reasoning; distributed power generation; power distribution control; reactive power control; substations; voltage control; AuRA-NMS; distributed generation; distributed voltage control; power system substations; reactive power control; real power control; statutory limits; transformer tap change control; voltage 11 kV; Case based reasoning; intelligent systems; power distribution control; voltage control;
fLanguage
English
Publisher
ieee
Conference_Titel
Power and Energy Society General Meeting, 2010 IEEE
Conference_Location
Minneapolis, MN
ISSN
1944-9925
Print_ISBN
978-1-4244-6549-1
Electronic_ISBN
1944-9925
Type
conf
DOI
10.1109/PES.2010.5589773
Filename
5589773
Link To Document