• DocumentCode
    2383917
  • Title

    New Fault Location Scheme for a Two- Terminal Transmission Line Using Synchronized Phasor Measurements

  • Author

    Brahma, S.M.

  • Author_Institution
    Dept. of Electr. Eng., Widener Univ., Chester, PA
  • fYear
    2006
  • fDate
    21-24 May 2006
  • Firstpage
    853
  • Lastpage
    857
  • Abstract
    This paper describes a new iterative method to locate fault on a single transmission line. The method uses synchronized voltage and current measurements from both terminals. Using positive sequence components of the pre-fault and fault waveforms, positive sequence source impedances are estimated. Using these source impedances and the line data, positive sequence bus impedance matrix (Zbus) is formed. Using the properties of Zbus, an iterative algorithm is proposed to locate the fault. This algorithm is applied to the data obtained from the EMTP simulation of two transmission lines. The simulation results show that though the method gives fairly accurate results for both medium and long transmission lines, its performance is better for medium and short lines
  • Keywords
    EMTP; fault location; iterative methods; phase measurement; power transmission faults; transmission line matrix methods; EMTP simulation; current measurements; fault location scheme; iterative method; positive sequence bus impedance matrix; positive sequence source impedances; synchronized phasor measurements; two-terminal transmission line; voltage synchronization; Current measurement; EMTP; Fault location; Impedance; Iterative algorithms; Iterative methods; Transmission line matrix methods; Transmission line measurements; Transmission lines; Voltage;
  • fLanguage
    English
  • Publisher
    ieee
  • Conference_Titel
    Transmission and Distribution Conference and Exhibition, 2005/2006 IEEE PES
  • Conference_Location
    Dallas, TX
  • Print_ISBN
    0-7803-9194-2
  • Type

    conf

  • DOI
    10.1109/TDC.2006.1668609
  • Filename
    1668609