Title
New Fault Location Scheme for a Two- Terminal Transmission Line Using Synchronized Phasor Measurements
Author
Brahma, S.M.
Author_Institution
Dept. of Electr. Eng., Widener Univ., Chester, PA
fYear
2006
fDate
21-24 May 2006
Firstpage
853
Lastpage
857
Abstract
This paper describes a new iterative method to locate fault on a single transmission line. The method uses synchronized voltage and current measurements from both terminals. Using positive sequence components of the pre-fault and fault waveforms, positive sequence source impedances are estimated. Using these source impedances and the line data, positive sequence bus impedance matrix (Zbus) is formed. Using the properties of Zbus, an iterative algorithm is proposed to locate the fault. This algorithm is applied to the data obtained from the EMTP simulation of two transmission lines. The simulation results show that though the method gives fairly accurate results for both medium and long transmission lines, its performance is better for medium and short lines
Keywords
EMTP; fault location; iterative methods; phase measurement; power transmission faults; transmission line matrix methods; EMTP simulation; current measurements; fault location scheme; iterative method; positive sequence bus impedance matrix; positive sequence source impedances; synchronized phasor measurements; two-terminal transmission line; voltage synchronization; Current measurement; EMTP; Fault location; Impedance; Iterative algorithms; Iterative methods; Transmission line matrix methods; Transmission line measurements; Transmission lines; Voltage;
fLanguage
English
Publisher
ieee
Conference_Titel
Transmission and Distribution Conference and Exhibition, 2005/2006 IEEE PES
Conference_Location
Dallas, TX
Print_ISBN
0-7803-9194-2
Type
conf
DOI
10.1109/TDC.2006.1668609
Filename
1668609
Link To Document